Cable and fuse tables for motorhome 12 V / 230 V systems

⚠️ Safety: 230 V wiring must be installed and tested by a qualified electrician (IEC/HD 60364-7-721). At 12 V the main hazard is fire from a short circuit – fuse every (+) cable at its source. Disconnect the batteries before working.

This page collects the tables for sizing cables and fuses. The principles are explained in 12 V batteries and distribution, charging and 230 V system. Always check the appliance manual too: where it gives a value, that value takes precedence.

Voltage drop – the formula

Copper cable resistance: R = ρ × L ÷ A, where ρ = 0.017 Ω·mm²/m (Victron), L is the total length (positive + negative) in metres and A is the cross-section in mm². Voltage drop: U = I × R.

Victron recommends a voltage drop of ≤ 2.5 %, which is about 0.3 V in a 12 V system. Victron's example: a 16 mm² cable 1.5 m long has 1.6 mΩ, so 200 A gives a 0.64 V drop – 5 %, which is too much.

Minimum cross-section: A = ρ × L × I ÷ Udrop. Victron's rule of thumb for lengths up to 5 m: A [mm²] ≈ I [A] ÷ 3.

Victron table – maximum current for a 0.259 V drop

Total cable length (positive + negative):

Cross-section mm² 5 m 10 m 15 m 20 m
0.75 2.3 1.1 0.8 0.6
1.5 4.5 2.3 1.5 1.1
2.5 7.5 3.8 2.5 1.9
4 12 6 4 3
6 18 9 6 5
10 30 15 10 8
16 48 24 16 12
25 75 38 25 19
35 105 53 35 26
50 150 75 50 38
70 210 105 70 53
95 285 143 95 71
120 360 180 120 90

Source: Victron Energy, Wiring Unlimited. The table covers voltage drop, not thermal current rating. With short, heavy cables, also check the cable maker's current rating.

Cable sizes and fuses from appliance manuals

Appliance Cable / fuse per manual
Shurflo Trail King 7 pump 10 A time-delay fuse; switch ≥ 15 A in (+); min. 2.5 mm²; 6–15 m: 4 mm²
Fiamma Aqua 8 pump 7.5 A fuse and 15 A switch in (+); min. 1.5 mm²; connect to the fuse box, not directly to the battery
Victron Orion XS 12/12-50A booster fuse 60–70 A; < 5 m: 16 mm²; 5–10 m: 25 mm²
Victron SmartSolar 100/30 battery fuse 35–40 A
Victron SmartSolar 100/50 battery fuse 55–70 A
Votronic VCC 1212-30 D+ signal wire fused at 1 A
13-pin socket (ISO 11446) pins 3, 9, 10: 2.5 mm² (Humbaur)
230 V hook-up cable, 16 A, 25 m 2.5 mm² (IEC 60364-7-721, Table 721.1)
230 V wiring in the vehicle min. 1.5 mm² (IEC 60364-7-721)

DC fuse types

Type Range (Victron) Typical use
Blade (automotive) up to 120 A, 32 V load circuits in the distribution unit
MIDI 23–200 A booster, solar controller, small inverter
MEGA 40–500 A main fuse, inverter
ANL 35–750 A main fuse, inverter
MRBF (battery terminal) 30–300 A directly on the battery post
Class T interrupt rating 20–200 kA LiFePO4 banks with high short-circuit current

Victron's rules:

EN 1648-2 requires fuses to ISO 8820.

Sizing example – step by step

  1. Load: 1000 W inverter. Current: 1000 W ÷ 12 V ≈ 83 A plus losses; use the current from the inverter manual.
  2. Length: 1.5 m to the battery and 1.5 m back, 3 m in total (≤ 5 m).
  3. Rule of thumb: 83 A ÷ 3 ≈ 28 mm², so take the next larger standard size, 35 mm².
  4. Check against the table: 35 mm² at 5 m carries 105 A at a 0.259 V drop – enough.
  5. Fuse: per the inverter manual and no higher than the cable rating (e.g. MEGA/ANL type).

Cable checklist

Sources

Every figure on this page comes from the sources below (standards, manufacturer manuals, regulations). Before installing, check the current edition of the standard and the manual of your specific device.

  1. Victron – Wiring Unlimited: theory (voltage drop)
  2. Victron – Wiring Unlimited: DC wiring and fuses
  3. IEC 60364-7-721:2017 – standard sample
  4. EN 1648-2:2018 – standard preview
  5. Shurflo Trail King 7 – product sheet
  6. Shurflo Trail King – installation instructions
  7. Fiamma Aqua 8 – manual
  8. Fiamma Aqua 8 – manual (electrical connection)
  9. Victron Orion XS 12/12-50A – installation
  10. Victron SmartSolar MPPT 100/30 and 100/50 – manual
  11. Votronic VCC 1212-30 – manual
  12. Humbaur – pin assignment 7/13-pin (ISO 11446)

Questions & comments

If you spot an inaccuracy, please report it to info@carbonzorro.com.

The content of this Knowledge base is for general information and illustration only. It is not technical or legal advice and does not replace standards, regulations, manufacturers’ instructions or the work of a qualified installer. Carbon Zorro Sp. z o.o. makes every effort to keep the information accurate and up to date, but does not guarantee that it is complete and accepts no liability for any consequences of its use.