Gas locker, leak testing, gas detectors and the G 607 inspection
⚠️ Safety: installation, modification and leak testing of an LPG system should be carried out by a qualified installer. This guide explains how systems are built – it does not replace EN 1949, the manufacturer’s instructions or an inspection.
This chapter complements the gas system layout. It covers where the cylinders are stored, how tightness is tested, which detectors to fit and how often the system is inspected.
Gas locker – EN 1949 requirements
| Requirement | Value / description | Clause |
|---|---|---|
| Separation from living area | sealed from the interior, access from outside only | 5.1.1 |
| Door to a garage (if any) | sealed, sill ≥ 50 mm | 5.1.6 |
| Cylinders | upright, valve up, secured at high and low level, securing without tools; pictogram label | 5.1.2.2 |
| Ventilation – low vent only | ≥ 2 % of locker floor area, minimum 10,000 mm² | 5.1.3 |
| Ventilation – low and high vent | each ≥ 1 % of floor area, minimum 5,000 mm² each | 5.1.3 |
| Low vent position | in the floor or in a wall at floor level; the cylinder must not block it | 5.1.3 |
| Distance from exhaust outlet | per figure 3 of the standard (250 mm or 300 mm depending on layout) or a heat shield – check the standard for your layout | 5.1.5 |
| Electrical equipment in the locker | none apart from extra-low-voltage gas controls; through cables in conduit ≥ 500 mm above the locker floor | IEC 60364-7-721, 721.528.3.1 |
LPG is heavier than air, so the low vent matters most: any leak drains out through it. promobil reminds readers that there must be no ignition source in the locker – not even LED lights.
Worked example: a locker floor of 40 × 60 cm = 2,400 cm² = 240,000 mm². With a low vent only: 2 % = 4,800 mm², but the minimum is 10,000 mm², so 10,000 mm² applies. With two vents: 1 % = 2,400 mm², so the minimum of 5,000 mm² each applies.
🛒 Products in the carbonzorro.com shop
Leak (tightness) testing
EN 1949 (clause 4.3) describes the test of the low-pressure section:
- Close the cylinder; open the appliance valves (burners off, hob closed).
- Connect the tester (gauge with pump) in place of the regulator or at a test point.
- Pressurise with 150 mbar of air.
- Wait 5 minutes for the pressure to stabilise (temperature equalisation).
- Measure for a further 5 minutes – the drop must not exceed 5 mbar.
- The test volume must be at least 700 cm³; short systems get an extra volume (e.g. GOK 150 Z with 600 cm³).
- Check high-pressure parts (cylinder–hose–regulator) with leak spray to EN 14291: no bubbles within 30 s.
- Issue a test record / declaration of conformity; a refuelling label is fitted to the vehicle (EN 1949).
Note – sources disagree: a polskicaravaning article on the G 607 inspection quotes a 10 mbar drop, whereas EN 1949:2021 and the GOK tester manual give 5 mbar. This guide uses the figure from the standard. Inspectors follow the procedure that applies in their country.
Quick home check (not a test): spray leak detector on the joints at the cylinder and regulator. Never look for leaks with a flame.
🛒 Products in the carbonzorro.com shop
- GOK gas leak tester type 150 Z with 600 cm³ additional volume - for LPG systems in motorhomes and boats, EN 1949
- GOK tester szczelności instalacji gazowej typ 4071, wylot 90°, RST 8 x RVS 8 - do kampera i przyczepy (Polish product page)
- GOK Spray do wykrywania nieszczelności 400 ml (Polish product page)
- Elektroniczny tester regulatora ciśnienia - Regulator Check LPG PRO (Polish product page)
Gas and carbon monoxide detectors
| Detector | Detects | Fitting / standard |
|---|---|---|
| CO alarm | carbon monoxide from incomplete combustion | for leisure vehicles EN 50291-2 (Caravan Club, Kidde) |
| LPG detector | propane/butane | low, near the floor – LPG is heavier than air (NKC) |
| Smoke alarm | smoke | EN 54-7 / BS 5446 (Caravan Club) |
| "Knock-out gas" detector | selected gases per maker's spec | often combined with LPG; check which gases it detects |
LPG–air mixtures are flammable at about 2–10 % gas (NKC), so a detector must warn well before that.
The Swedish agency MCF recommends a powder extinguisher of at least 2 kg in caravans and motorhomes.
🛒 Products in the carbonzorro.com shop
- 3GAS Alarm czujnik czadu CO, LPG i narkogazów 12 V / 24 V - do kampera i przyczepy (Polish product page)
- TrioGas trivalent gas leak detector grey panel mount
- CBE BMTCO - detektor tlenku węgla, 12 V, 15 mA, szary łupkowy (Polish product page)
- CBE BMTG - LPG and soporific gas detector, 12 V, grey
- Carbest GasCube detektor gazu LPG i gazów usypiających - montaż stały, 12 do 30 V (Polish product page)
- Detektor gazu GAS-pro III CO-tlenek węgla (Polish product page)
Gas level indicators
To check how much gas is left in a steel cylinder, use scales (e.g. iGasView), an ultrasonic sensor (Gaslevel, Truma LevelControl, Brunner W8 Smart), or the gauge on a composite or GasBank cylinder.
🛒 Products in the carbonzorro.com shop
Periodic gas inspections
| Country | Requirement | Source |
|---|---|---|
| Germany | G 607 before first use, after changes and every 24 months (§60 StVZO); mandatory since 19.06.2025; not part of the MOT-style HU; yellow test book and sticker | StVZO, DVFG |
| Poland | no mandatory periodic inspection | – |
| Netherlands | not mandatory; NKC advises a check every 2 years | NKC |
| Sweden | leak check at each cylinder change or at least every 2 years; inspection voluntary | MCF, Bilprovningen |
| UK | annual habitation check recommended, not a legal requirement | Approved Workshops, Caravan Club |
Full overview: country rules.
Gas maintenance calendar
| When | Task | Source |
|---|---|---|
| every cylinder change | spray the cylinder–hose joint; check the seal | MCF, EN 1949 |
| before the season | hoses (cracks, date), gas filter, locker vents | Truma, promobil |
| per filter instructions | replace the filter cartridge (Truma/GOK sell spares) | filter manual |
| every 2 years | gas inspection (mandatory G 607 in Germany) | StVZO, NKC, MCF |
| clamped hoses | replace every 2 years | NKC |
| LPG hoses (UK) | replace every 3 years | Caravan Club |
| regulator and high-pressure hoses | replace within 10 years of manufacture | Truma, promobil |
| before a ferry / refuelling | switch off gas appliances including the fridge; close the main valve on ferries | MCF |
Troubleshooting
| Symptom | Likely cause | What to do |
|---|---|---|
| No gas after a jolt or hard braking | crash sensor (CS) tripped | check the system, reset per regulator manual |
| No gas, cylinder full | appliance valve closed, filter clogged | open the valve, replace the filter cartridge |
| Smell of gas | leak | close the cylinder, ventilate, no flames or switches; get it serviced |
| CO alarm | incomplete combustion, blocked flue | switch off, ventilate, leave the vehicle; get it serviced |
| Flame goes out when knob released | thermocouple / flame failure device | have the appliance serviced |
| Pressure drop during test | leaking joint or valve | locate with spray, fix, retest |
Locker and inspection checklist
- [ ] locker sealed from the interior, external access
- [ ] vents sized to EN 1949 and unobstructed
- [ ] cylinders secured top and bottom
- [ ] no electrical equipment in the locker (except extra-low-voltage gas controls)
- [ ] leak test with written record
- [ ] CO (EN 50291-2) and LPG detectors fitted
- [ ] extinguisher within reach
Sources
Every figure on this page comes from the sources below (standards, manufacturer manuals, regulations). Before installing, check the current edition of the standard and the manual of your specific device.
- EN 1949:2021 – standard preview (iTeh)
- SIST EN 1949:2022 – standard sample (tightness test, 4.3)
- GOK – leak tester 150 Z manual
- Polski Caravaning – G607 – przegląd instalacji gazowej (PL)
- Inspektomat – przegląd instalacji gazowej w przyczepie (PL)
- IEC 60364-7-721:2017 – standard sample (721.528.3.1)
- § 60 StVZO (DE)
- DVFG – G 607-Prüfung für Freizeitfahrzeuge
- NKC – Gasgebruik in de camper
- promobil – Basiswissen Gas im Wohnmobil
- The Caravan Club – fire safety
- Kidde – CO alarms for holidays / RV (EN 50291-2)
- MCF (SE) – Gasol i husvagn och husbil
- Bilprovningen – tips för husvagn och husbil
- NCC Academy – gas competence matrix
- Approved Workshops – habitation checks
- The Caravan Club – LPG advice
If you spot an inaccuracy, please report it to info@carbonzorro.com.
The content of this Knowledge base is for general information and illustration only. It is not technical or legal advice and does not replace standards, regulations, manufacturers’ instructions or the work of a qualified installer. Carbon Zorro Sp. z o.o. makes every effort to keep the information accurate and up to date, but does not guarantee that it is complete and accepts no liability for any consequences of its use.